What is earthing?
Earthing, called grounding in the US, is the connection of parts of an electrical system to the ground through a conductor.
Earthing or grounding
Both words name the same connection. EASA rules for aerodromes say earthing. FAA advisory circulars and the US National Electrical Code (NEC) say grounding. This page uses earthing and keeps “ground” in the names of FAA parts, such as ground rod.
Why earthing matters
Earthing protects people when insulation fails. In a household appliance, the third wire connects to the metal case. If a live wire touches the case, the earth connection keeps the case voltage near zero and the breaker trips. Without the earth connection, the case stays live and a severe shock is possible.
The size of the current decides the harm:
- 1 milliampere (mA) is the threshold of sensation.
- Currents below 5 mA are apparently harmless.
- From 5 to 30 mA, the current can cause sustained muscle contraction.
- Above 300 mA through the heart, death may occur.
A ground fault circuit interrupter (GFCI) compares the current in the live and neutral wires. It usually trips when the leakage current is above 5 mA. The neutral wire is also tied to ground at two points, so it sits at zero volts relative to ground.
Earthing systems: TN and TT
The International Electrotechnical Commission (IEC) uses a letter code for the way a system earths its neutral. Two arrangements are common:
- TT system: the neutral is earthed only at the distribution transformer. The building gets its protective earth from a local earth electrode.
- TN system: the neutral is earthed at any available point outside the building, such as the transformer, poles and service entrance.
In the United States, the equipment grounding conductor joins the neutral at the service entrance. After that point, the neutral and the equipment grounding conductor stay separate.
Earth electrode and earth resistance
An earth electrode, such as a ground rod, makes the physical contact with the soil. The earth resistance of the electrode sets how much voltage appears on it when current flows in. The FAA limits each ground rod to 25 ohms in its specification for electrical manholes.
In soil with high resistivity, such as well-drained sand or dry desert, the designer may need more rods or other electrodes to reach 25 ohms. The FAA also notes that 25 ohms does not make a grounding system satisfactory by itself.
The test is a fall-of-potential test to ANSI/IEEE Standard 81. The contractor does it before the rod joins other electrodes. A clamp-on ground impedance meter is an accepted alternative.
Earth potential rise
When fault current enters the ground, current through the earth resistance creates a voltage across it. The electrode reaches a voltage relative to distant earth, and the voltage spreads outward in the soil as a ground potential gradient. Step potential is the voltage between the feet of a person who stands near the electrode. Touch potential is the voltage between the electrode and the feet of a person who touches it.
Worked example: a ground fault sends 100 A into a rod with 25 Ω of earth resistance. By V = IR, the rod reaches 100 A × 25 Ω = 2,500 V relative to distant earth. A lower earth resistance gives a lower voltage for the same current.
Earthing on an airfield
FAA AC 150/5340-30J describes a counterpoise for airfield lighting. The counterpoise is a bare solid copper conductor, at least No. 6 American wire gauge (AWG). Ground rods, at most 500 ft (152 m) apart, connect to it with exothermic welds. It gives lightning energy a low-resistance path into the earth, and it protects underground power and control cables. The designer checks whether the soil harms copper.
The counterpoise is a separate system from the equipment grounding conductor. The equipment grounding conductor gives ground-fault current a return path on parallel voltage circuits only. Series circuits do not use it.
The AC gives two installation methods:
- Equipotential method: the conductor lies about 8 inches (200 mm) above the cable or duct. The installer bonds it to the light bases and to all metallic parts on the output side of the constant current regulator. All the parts then rise and fall to the same potential.
- Isolation method: the conductor lies halfway between the pavement edge and the light base, 8 inches (200 mm) below grade. Each light base has its own electrode with an earth resistance below 25 Ω.
The designer uses one method on a circuit, not both. The installer also bonds each light fixture to the ground lug of its light base. A series lighting circuit is non-grounded. An unintentional ground does not shut the system down. The FAA still requires an insulation resistance to ground of at least 50 megohms for non-grounded series circuits. See closed circuit and lighting circuit .
Earthing and aircraft refuelling
EASA rule ADR.OPS.D.060 of Regulation (EU) No 139/2014 sets requirements for the aerodrome refuelling procedure. The procedure must cover the bonding of the aircraft and the fuel supply, and the application of earthing procedures.
TarmacView does not measure earth resistance. It inspects the lights with a drone.
Frequently Asked Questions
- What is earthing in electricity?
- Earthing is the connection of parts of an electrical system to the ground through a conductor. A common case is the metal case of an appliance. If a live wire touches a grounded case, the case voltage stays near zero and a breaker trips.
- Is earthing the same as grounding?
- Yes. Both words name the connection of parts of an electrical system to the ground. EASA rules for aerodromes say earthing. FAA advisory circulars and the US National Electrical Code (NEC) say grounding.
- What is the difference between a TN system and a TT system?
- In a TT system the neutral is earthed only at the distribution transformer, and the building gets its protective earth from a local earth electrode. In a TN system the neutral is earthed at many points outside the building.
- What is earth potential rise?
- It is the voltage that a grounding electrode reaches relative to distant earth when fault current flows into the ground. The voltage equals the current times the resistance of the earth connection. A 100 ampere fault into a 25 ohm rod gives 2,500 volts.
- What is a counterpoise on an airfield?
- A counterpoise is a bare copper conductor, buried along airfield lighting cables, that gives lightning energy a low-resistance path into the earth. It is a separate system from the equipment grounding conductor that carries fault current.
- What earth resistance does the FAA allow for a ground rod?
- The FAA construction specification for electrical manholes sets a maximum of 25 ohms for each ground rod. AC 150/5340-30J says soil with high resistivity may need more rods to meet the 25 ohms. It also notes that 25 ohms is not necessarily a satisfactory value for a grounding system.
- How do you measure earth resistance?
- The FAA specification tests each ground rod with the fall-of-potential method of ANSI/IEEE Standard 81. A clamp-on ground impedance meter is an alternative. The test is done before the rod joins other electrodes.
- Why does a ground fault interrupter trip at 5 milliamperes?
- A ground fault circuit interrupter (GFCI) compares the current in the live and neutral wires and trips when they differ. It is usually set to trip above 5 milliamperes of leakage current, the accepted maximum harmless shock.
References
- openstax-up2-10-6
- University Physics Volume 2, section 10.6: Household Wiring and Electrical Safety OpenStax
- openstax-cp2e-23-8
- College Physics 2e, section 23.8: Electrical Safety: Systems and Devices OpenStax
- nist-ieee-neutral-earthing
- The Effect of Neutral Earthing Practices on Lightning Current Dispersion in a Low-Voltage Installation (Mansoor and Martzloff, IEEE Trans. Power Delivery, 1998) NIST / IEEE
- osha-1910-269-app-c
- 29 CFR 1910.269 Appendix C, Protection From Hazardous Differences in Electric Potential OSHA
- openstax-up2-9-4
- University Physics Volume 2, section 9.4: Ohm's Law OpenStax
- faa-ac-150-5340-30j
- AC 150/5340-30J, Design and Installation Details for Airport Visual Aids FAA
- faa-ac-150-5370-10h
- AC 150/5370-10H, Standard Specifications for Construction of Airports FAA
- easa-ear-aerodromes
- Easy Access Rules for Aerodromes (Regulation (EU) No 139/2014), ADR.OPS.D.060 EASA