← AVIATION GLOSSARY
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Aviation glossary

What is Power Factor?

Electrical engineering · Airfield lighting 8 languages
Definition
The power factor is the ratio of the real power a load uses to the apparent power the source supplies in an AC circuit.

The power factor is the ratio of the real power a load uses to the apparent power the source supplies in an AC circuit.

AC means alternating current. A load is any device that takes power from the source.

Real, reactive and apparent power

AC circuits have three kinds of power. Real power (P) is the average power that does useful work or makes heat. Its unit is the watt (W). Reactive power (Q) is the power that inductors and capacitors store and return. It does no work. Its unit is the volt-ampere reactive (var). Apparent power (S) is the root mean square (RMS) voltage multiplied by the RMS current. Its unit is the volt-ampere (VA).

For a single-phase load with a phase angle θ between voltage and current, the three powers are:

  • P = V × I × cos θ
  • Q = V × I × sin θ
  • S = V × I

The power triangle

The three powers form a right triangle. P and Q are the short sides, and S is the long side. The triangle gives S² = P² + Q², and so P = S cos θ and Q = S sin θ. The angle θ is the power factor angle.

Power factor formula and unit

The power factor is P divided by S. For sine waves it equals cos θ:

power factor = P / S = P / (V × I) = cos θ

The power factor has no unit, because it divides one power by another. Its value lies between 0 and 1. A resistive load has a power factor of 1, because voltage and current are in phase. A purely inductive or purely capacitive load has a power factor of 0. The current is 90 degrees out of phase, so the load uses no real power.

Some sources give the power factor as a percentage. A power factor of 0.8 is then 80 percent. The units of the three powers differ, so do not add them. A kilowatt (kW) is 1,000 W. A kilovolt-ampere (kVA) is 1,000 VA. A kilovar (kvar) is 1,000 var.

Lagging and leading

An inductive load, such as a motor, makes the current lag the voltage. The power factor is lagging, and Q is positive. A capacitive load makes the current lead the voltage. The power factor is leading, and Q is negative. The value is a positive number. Add the word lagging or leading to show which case it is.

LoadCurrent compared with voltagePower factorSign of Q
ResistiveIn phase10
Inductive (motor)LagsLaggingPositive
CapacitiveLeadsLeadingNegative

How to find the power factor

Measure the real power P. Measure the RMS voltage V and the RMS current I. Then divide P by V × I. If you know S and Q instead, use P = √(S² − Q²).

Worked example. A load takes 4.8 kW and 7.2 kvar. The apparent power is S = √(4.8² + 7.2²) = √(23.04 + 51.84) = √74.88 = 8.65 kVA. The power factor is 4.8 / 8.65 = 0.55 lagging. The angle θ is about 56.3 degrees.

Why a low power factor matters

A source supplies the reactive power as well as the real power. The reactive power flows through the lines, but it does no work. Any power factor below 1 means that the wiring carries more current than the real power needs. The current is I = P / (V × pf), so for the same P and V it rises as the power factor falls.

At a power factor of 0.7, the current is 1 / 0.7 = 1.43 times the current at a power factor of 1. That is about 43 percent more. The extra current causes extra heat in the wires. In the 20 kW motor example below, the line loss is 3.86 kW at 0.6 and 1.47 kW after correction. The wiring must carry the current that the apparent power gives. Size it for kVA, not only for kW.

What causes a low power factor

Inductive loads cause a lagging power factor. Motors are the usual example. A capacitive load causes a leading power factor. A circuit with both can have a value near 1, because the leading and lagging reactive power cancel.

Power factor correction

Correction means adding reactive power of the opposite sign close to the load. For an inductive load, the usual method is a capacitor in parallel with the load. The capacitor supplies reactive power, so the source supplies less. The real power of the load does not change.

The size of the capacitor follows from the power triangle. If the load has real power P and a power factor angle θ1, its reactive power is P × tan θ1. For a target angle θ2, the new reactive power is P × tan θ2. The capacitor supplies the difference:

Qc = P × (tan θ1 − tan θ2)

Worked example. The load above takes 4.8 kW at 0.55 lagging, so θ1 = 56.3 degrees and tan θ1 = 1.5. The target is 0.9 lagging, so θ2 = cos⁻¹ 0.9 = 25.8 degrees and tan θ2 = 0.483.

  • Qc = 4.8 kW × (1.5 − 0.483) = 4.88 kvar
  • The reactive power drops from 7.2 kvar to 2.32 kvar.
  • On a 120 V circuit, the load current falls from 72.1 A to 44.4 A, a cut of 38 percent.

A second example uses a 20 kW motor at 0.6 lagging on a 120 V line. The apparent power is 20 / 0.6 = 33.3 kVA, and Q is 26.7 kvar. A 22 kvar capacitor leaves 4.7 kvar. The line current falls from 278 A to 171 A. The line loss falls from 3.86 kW to 1.47 kW.

A capacitor that is too large turns the circuit from lagging to leading, so the correction needs a calculation and not a guess.

Common mistakes

  • Treating power factor as a unit. It is a ratio with no unit.
  • Adding watts and var. The powers add as the sides of a right triangle, not as numbers.
  • Leaving out lagging or leading. The value 0.8 alone does not say which case it is.
  • Sizing a cable for kW. The cable carries the current that S gives.

Power factor at an airfield

Constant current regulators (CCRs) supply the series circuits of airfield lights. Advisory circular (AC) 150/5340-30J of the Federal Aviation Administration (FAA) tells the designer to find the kVA input of a CCR before choosing standby power. The kVA input is the rated kW divided by the CCR efficiency and the power factor. The example in the circular uses 30 kW, an efficiency of 0.92 and a power factor of 0.7. This gives 30 / (0.92 × 0.7) = 46.6 kVA. A measurement of 2,400 V at 17.0 A gives 40.8 kVA. The circular says that the measured value is normally lower. It also says to use the calculated value for design.

The circular also says that:

  • Capacitors can raise the power factor of a regulator above 0.7. The regulator manufacturer gives the recommendation.
  • Calculations that use the power factor change with the circuit load. The designer should check the lowest and highest loads.
  • Light-emitting diode (LED) fixtures, signs and addressable components can be non-linear or reactive loads. Their switching power supplies can add a capacitive characteristic. The designer should consult the CCR manufacturer.
  • Devices that are not certified for the high voltage series circuit can give a poor power factor. This can cause unexpected CCR shutdowns and start-up problems.

Frequently Asked Questions

What is power factor?
Power factor is the ratio of real power to apparent power in an AC circuit. For sine waves it equals the cosine of the phase angle between voltage and current. A resistive circuit has a power factor of 1. A purely inductive or purely capacitive circuit has a power factor of 0.
What is the formula for power factor?
Power factor is P divided by S, where P is the real power in watts and S is the apparent power in volt-amperes. For a single-phase load, S is the voltage multiplied by the current. This gives power factor = P / (V × I) = cos θ.
What is the unit of power factor?
Power factor has no unit. It is a ratio of two powers, so it is a plain number from 0 to 1. Some sources give it as a percentage. The three powers it relates have units: real power in watts (W), reactive power in var, and apparent power in volt-amperes (VA).
What is a good power factor?
A power factor of 1 is the best value, because all of the current does useful work. Any value below 1 means the wiring carries more current than the real power needs. At 0.7 the current is about 43 percent higher than at 1.
What is the difference between a lagging and a leading power factor?
A lagging power factor means the current lags the voltage, which happens with inductive loads such as motors. A leading power factor means the current leads the voltage, which happens with capacitive loads. The value is a positive number, and the word lagging or leading shows which case it is.
What is the power triangle?
The power triangle is a right triangle. Real power P and reactive power Q are the two short sides. Apparent power S is the long side. It gives S squared = P squared + Q squared. The angle between P and S is the power factor angle, and its cosine is the power factor.
How is a low power factor corrected?
For inductive loads, the usual method is to connect capacitors in parallel with the load. They supply reactive power, so the source supplies less. The load keeps the same real power. In one university example, a capacitor of 4.88 kvar raises 0.55 lagging to 0.9 lagging. It cuts the current by 38 percent.
Does power factor matter for airfield lighting?
Yes, for the power supply of series lighting circuits. FAA AC 150/5340-30J divides the rated kW of a constant current regulator by its efficiency and power factor to find the kVA input. Devices that are not certified for the circuit can give a poor power factor and unexpected regulator shutdowns.

References

louisville-ee220-l12
EE 220, Lesson 12: Power in AC Circuits University of Louisville, J. B. Speed School of Engineering

This is a reference entry. TarmacView provides drone inspection services and doesn't sell the equipment or materials described in this glossary.

Get Started Need your airfield lighting verified? TarmacView inspects approach, runway and taxiway lights and the runway surface by drone, during full airport operation. The lighting protocol comes the same day.
Keep reading

Learn more

03 PAGES
Reactive Power (Q)
glossary

Reactive Power (Q)

Reactive power (Q) is AC power that swings between source and load and does no work. Unit: var. Formula, power triangle, worked examples and airfield use.

Power
glossary

Power

Power is the rate of doing work or transferring energy, P = W / t, measured in watts (1 W = 1 J/s). Formulas, units, worked examples and airfield lighting.

Watt (W)
glossary

Watt (W)

The watt (symbol W) is the SI unit of power, one joule per second. Formulas P = W/t and P = V x I, kilowatts, watt-hours and horsepower.