What is a beam pattern?
A beam pattern is the luminous intensity of a light source in each direction, shown as a diagram of candela against angle.
What a beam pattern describes
Luminous intensity is the density of luminous flux in one direction. The unit is the candela (cd). A beam pattern gives this value for many directions. It shows where the light goes, and not only how much light the source emits.
The International Commission on Illumination (CIE) calls the full set of values the luminous intensity distribution. It is a presentation of the intensity as a function of direction, by curves or by tables. A distribution curve is the same data drawn as a curve. It is normally drawn in polar coordinates, with the origin at the photometric centre of the light.
How a beam pattern is shown
- Distribution curve. A polar plot of the candela in one plane through the light. It is the most common way to show the distribution of a lamp or luminaire.
- Table. A list of candela values at set angles. One exchange format for the table is the IES photometric file (the IES LM-63 format).
- Isocandela diagram. A flat plot of horizontal and vertical angles with closed curves on it. Each curve joins the directions that have the same intensity. Annex 14 and CS-ADR-DSN use this form for airfield lights.
The CIE term for such a curve is the iso-intensity curve. The CIE says that the words isocandela curve and isocandela line are no longer in use. ICAO and EASA still use “isocandela diagram”, so this page uses the same words for airfield lights.
How a beam pattern is measured
A goniophotometer measures the intensity at many angles around the light. The CIE defines it as a photometer for the directional light distribution of sources and luminaires.
Luminaire photometry commonly uses the (C, γ) coordinate system. The C-planes are half-planes that rotate round the vertical line through the photometric centre. The (A, α) and (B, β) systems also exist. Floodlights are customarily tested with Type B photometry, where the angles start at the primary aiming axis. Most other luminaires use Type C. Check which system a report uses before you compare two curves.
Symmetric and asymmetric patterns
The CIE defines a symmetrical distribution as one with at least one axis of symmetry or at least one plane of symmetry. Some texts use the word for a distribution that is the same in every plane. The CIE discourages this use. State the axis or the plane when you describe a pattern as symmetric.
A pattern that differs between the horizontal and the vertical plane needs two angles. The NEMA system for floodlights does this. A luminaire classified 1×3 has one digit for the horizontal field angle and one for the vertical field angle.
The ellipses in the Annex 14 diagrams are symmetrical about the vertical and horizontal axes of the diagram. They are not centred on the horizon. For an approach light 641 m or more from the threshold, the main beam covers 2.5° to 13.5° above the horizontal. The beam is aimed upward.
Beam angle and field angle
A beam angle gives one width of the pattern. It does not give the intensity inside it. The CIE defines the beam angle as the angle between the two directions where the intensity is 50% of the centre beam intensity. It is a full angle, and not a half angle.
The IES and ANSI standards use 50% of the maximum intensity or of the centre beam intensity, depending on the standard. The field angle is the same angle at 10%. If the maximum is 1,000 cd and 500 cd occurs 20° from the centre, the beam angle is 40°.
Airfield rules use a third word, beam spread. The CIE defines it as the total angle within which the illuminance on a plane normal to the beam axis exceeds 10% of the maximum. It adds that the angle is sometimes calculated at 50%. For obstacle lights, Annex 14 and CS-ADR-DSN measure it from the horizontal plane.
Beam patterns of airfield lights
Each type of airfield light has its own isocandela diagram. Annex 14 gives them in Appendix 2, and CS-ADR-DSN gives them in CS ADR-DSN.U.940. These are examples, read from the figures:
| Light | ICAO figure | CS figure | Minimum average, main beam | Main beam minimum | Outer curves |
|---|---|---|---|---|---|
| Approach centre line and crossbars, white | A2-1 | U-5 | 20,000 cd | 10,000 cd | 2,000 cd and 1,000 cd |
| Runway edge, 45 m wide runway, white | A2-9 | U-13 | 10,000 cd | 5,000 cd | 1,000 cd and 500 cd |
| Runway edge, 60 m wide runway, white | A2-10 | U-14 | 10,000 cd | 5,000 cd | 1,000 cd and 500 cd |
The two edge light diagrams carry the same intensities. The 60 m diagram is wider. Its main beam reaches 6.5° to each side of the vertical plane, against 5.5° for the 45 m diagram. EASA also asks designers to consider the light distribution of runway edge lights when the runway is wider than 60 m.
The diagrams set the following for the main beam:
- The diagram shows the minimum allowed intensity.
- The average intensity is the arithmetic average of the values at the grid points inside the curve and on its perimeter.
- In the main beam of the lights of Figures A2-1 to A2-10, the maximum intensity is at most three times the minimum. Annex 14 requires this, and it sets the same ratio for the lights of Figures A2-12 to A2-20.
- No deviations are acceptable in the main beam when the fixture is properly aimed.
Colour is part of the pattern. The colour is measured at the centre and at the limits of the innermost curve. It is checked again at the outermost curve, to find a colour shift that could confuse the pilot.
Aim
A beam pattern gives the required intensity only when the light is aimed correctly. The standards therefore specify the aim of the beam axis:
| Distance of an approach light from the threshold | Vertical coverage of the main beam |
|---|---|
| Threshold to 315 m | 0° to 11° |
| 316 m to 475 m | 0.5° to 11.5° |
| 476 m to 640 m | 1.5° to 12.5° |
| 641 m and beyond | 2.5° to 13.5° |
- Annex 14 requires crossbar lights more than 22.5 m from the centre line to be toed in 2°. CS ADR-DSN recommends the same. All other approach lights are parallel to the runway centre line.
- FAA Order JO 6850.2C requires the beam axis of all approach lights to be parallel to the extended runway centreline.
- FAA AC 150/5340-30J orients the beam axis of a runway end identifier light unit 15° outward and 10° above the horizontal. This is for a unit without baffles. With optical baffles it is 10° outward and 3° above the horizontal.
- For the lights of Figures A2-1 to A2-21, Annex 14 requires the main beam to be within one-half degree of the specified aim.
Checking a beam pattern on an airfield
Annex 14 deems a light unserviceable when the main beam average intensity is less than 50% of the value in Appendix 2. EASA says that the maintenance level is always above this 50% level, so that corrective action can start before the light fails.
EASA recommends photometric measurements at suitable intervals for every runway type. For a category II or III precision approach runway, it recommends in-field measurement of intensity, beam spread and orientation of approach and runway lights. It recommends to measure all lights as far as practicable and to compare them with the figure in CS ADR-DSN.U.940. The frequency is not less than twice a year for in-pavement lights and not less than once a year for other lights.
A drone survey does not give a candela value, because that needs a calibrated photometer. TarmacView reports the output of a light relative to the neighbouring lights.
Frequently Asked Questions
- What is a beam pattern?
- A beam pattern is the luminous intensity of a light source in each direction. It shows where the light goes, and not only how much the source emits. It is drawn as a diagram of candela against angle.
- What is a luminous intensity distribution curve?
- A luminous intensity distribution curve is a curve that gives the luminous intensity of a source as a function of direction. The CIE says it is normally drawn in polar coordinates, with the origin at the photometric centre of the light.
- What is the difference between symmetric and asymmetric light distribution?
- A symmetric distribution has at least one axis or plane of symmetry. An asymmetric distribution has none. The CIE says to avoid the word symmetrical for a rotationally symmetrical distribution, so state the axis or the plane.
- What is the difference between a beam pattern and a beam angle?
- A beam pattern gives the intensity in every direction. A beam angle is one number from it. It is the angle between the two directions where the intensity is 50% of the maximum, or of the centre beam intensity.
- What is the difference between a beam pattern, a beam spread and a light pattern?
- A beam pattern gives the intensity of one light in every direction. Beam spread is one angle that describes the width of that beam. A light pattern is the shape that a group of lights forms, for example an approach lighting system.
- How do airfield lights specify the beam pattern?
- Each type of light has its own isocandela diagram. ICAO Annex 14 gives the diagrams in Appendix 2, and CS-ADR-DSN gives them in CS ADR-DSN.U.940. A diagram sets the minimum intensity inside closed curves, and the main beam is the innermost curve.
- How is a beam pattern measured?
- A goniophotometer measures the intensity at many angles around the light. The CIE defines it as a photometer for the directional light distribution of sources and luminaires. The results are stored as a table of candela values against angle.
- How do you check the beam pattern of an airfield light for compliance?
- Measure the intensity in the field and compare it with the isocandela diagram. EASA recommends in-field measurement of intensity, beam spread and orientation for a category II or III runway. ICAO deems a light unserviceable when the main beam average falls below 50% of the specified value.
References
- bipm-candela
- SI base unit: candela (cd) BIPM
- cie-ilv-luminous-intensity
- International Lighting Vocabulary (CIE S 017:2020), e-ILV entry 17-21-045, luminous intensity CIE
- cie-ilv-distribution-curve
- International Lighting Vocabulary (CIE S 017:2020), e-ILV entry 17-25-091, distribution curve of luminous intensity CIE
- cie-ilv-intensity-distribution
- International Lighting Vocabulary (CIE S 017:2020), e-ILV entry 17-29-037, luminous intensity distribution CIE
- cie-ilv-iso-intensity
- International Lighting Vocabulary (CIE S 017:2020), e-ILV entry 17-29-041, iso-intensity curve CIE
- cie-ilv-symmetrical
- International Lighting Vocabulary (CIE S 017:2020), e-ILV entry 17-29-038, symmetrical luminous intensity distribution CIE
- cie-ilv-beam-angle
- International Lighting Vocabulary (CIE S 017:2020), e-ILV entry 17-27-077, beam angle CIE
- cie-ilv-beam-spread
- International Lighting Vocabulary (CIE S 017:2020), e-ILV entry 17-25-087, beam spread CIE
- cie-ilv-goniophotometer
- International Lighting Vocabulary (CIE S 017:2020), e-ILV entry 17-25-026, goniophotometer CIE
- cie-ilv-c-gamma
- International Lighting Vocabulary (CIE S 017:2020), e-ILV entry 17-25-090, (C, gamma) coordinate system CIE
- doe-caliper-20
- CALiPER Application Summary Report 20: LED PAR38 Lamps (November 2012, addendum September 2013) US Department of Energy
- doe-caliper-15
- CALiPER Application Summary Report 15: LED Floodlights (May 2012) US Department of Energy
- lbnl-ies2rad
- ies2rad(1), Radiance manual page Lawrence Berkeley National Laboratory
- easa-ear-aerodromes
- Easy Access Rules for Aerodromes (Regulation (EU) No 139/2014), CS-ADR-DSN Issue 7 EASA
- icao-annex-14-vol-i-9ed
- Annex 14 Volume I, Aerodromes, 9th edition ICAO
- faa-jo-6850-2c
- FAA Order JO 6850.2C, Visual Guidance Lighting Systems FAA
- faa-ac-150-5340-30j
- AC 150/5340-30J, Design and Installation Details for Airport Visual Aids FAA
This is a reference entry. TarmacView provides drone inspection services and doesn't sell the equipment or materials described in this glossary.


