← AVIATION GLOSSARY
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Aviation glossary

What is a Constant Current Regulator (CCR)?

Airfield lighting · Electrical systems 8 languages
Definition
A constant current regulator (CCR) is a power supply that holds an airport series lighting circuit at the current of the selected brightness step.

A constant current regulator (CCR) is a power supply that holds an airport series lighting circuit at the current of the selected brightness step.

The lights of a runway or taxiway row share one series circuit, and the CCR sets how bright they are. CCR is the short form of constant current regulator. The FAA specification calls the cabinet a regulator and the unit that watches it a monitor.

How it works

The lights of a row sit on one series circuit, so the same current passes through each light. Each light connects through an isolation transformer. The transformer isolates the light unit from the high voltage of the series circuit. When a lamp filament opens, the transformer keeps the primary circuit closed (AC 150/5340-30J 3.5.3). The CCR holds the current while the load changes.

A CCR keeps its output current in range for any load from a short circuit to 100 percent (AC 150/5345-10H 3.3.1.1). It also does so when up to 30 percent of the transformer secondary windings are open (3.3.1.2). After a step change it stabilizes the current within 5 seconds, and holds it within 0.1 A for a 6.6 A unit (3.3.7).

The voltage follows the load. The FAA gives the example of a fully loaded 30 kW CCR at 6.6 A, which develops about 4,545 V (AC 150/5340-26C 5.2.4). The open-circuit voltage limit applies with the open-circuit protection disabled. It is 4,250 V or two times the rated power divided by the rated current, whichever is greater (AC 150/5345-10H 3.3.9). For a 30 kW, 6.6 A unit the second value is about 9,090 V.

Regulator designs

AC 150/5340-26C 5.2 sorts regulators in two ways. A unit is air cooled or liquid (usually oil) filled. A unit is also ferromagnetic or electronic. Ferromagnetic types typically use a ferroresonant network circuit or a saturable reactor. The same AC tells airports to keep spare printed circuit boards for each type of CCR. It adds critical parts such as silicon controlled rectifiers (SCRs).

IEC 61820-3-2:2023 covers power electronic converter systems that power series-circuit lighting. The design affects how a CCR behaves with some loads. For Mode 1 runway guard lights, the FAA says to check with the manufacturer that the CCR suits flashing lights. It notes that this is typically a ferroresonant type (AC 150/5340-30J 4.8.6.1.1). For a REIL, the CCR must accept a pulsing load that may have reactive components (7.5.2.1.2).

Why the current sets the brightness

A series circuit controls brightness through the current. The FAA steps for the common runway edge systems are:

SystemStepLamp currentBrightness
HIRL56.6 A100 percent
HIRL45.2 A25 percent
HIRL34.1 A5 percent
HIRL23.4 A1.2 percent
HIRL12.8 A0.15 percent
MIRL and MITL36.6 A100 percent
MIRL and MITL25.5 A30 percent
MIRL and MITL14.8 A10 percent

The relation is not linear. A drop in current from 6.6 A to 5.2 A, about a fifth, cuts the brightness to 25 percent. A parallel circuit sets brightness with voltage instead. For MIRL on a parallel circuit, 120 V gives full brightness (AC 150/5340-30J 2.6.4.1 and 2.6.4.2). The HIRL entry has the same table.

Light output must rise and fall with the CCR current. For an LED fixture on a CCR, FAA Engineering Brief 67D says the intensity must follow the curve of an incandescent lamp (paragraph 1.0). A 3-step CCR may not reduce LED light enough at its lowest step. The FAA says a 5-step CCR is necessary to control LED high intensity taxiway centerline systems (AC 150/5340-30J 4.8.5.2).

Types, classes and steps

AC 150/5345-10H 1.2 defines three types:

  • L-827: regulator monitor.
  • L-828: regulator without monitoring.
  • L-829: regulator with monitoring.

The classes are 6.6 A (Class 1) and 20 A (Class 2). Style 1 has three brightness steps and Style 2 has five. The nominal currents and allowed ranges (Table 1) are:

Class and styleStep currents, step 1 to the top (allowed range in A RMS)
Class 1, Style 14.8 A (4.70 to 4.90), 5.5 A (5.40 to 5.60), 6.6 A (6.50 to 6.70)
Class 1, Style 22.8 A (2.70 to 2.90), 3.4 A (3.30 to 3.50), 4.1 A (4.00 to 4.20), 5.2 A (5.10 to 5.30), 6.6 A (6.50 to 6.70)
Class 2, Style 28.5 A (8.20 to 8.80), 10.3 A (10.00 to 10.60), 12.4 A (12.10 to 12.70), 15.8 A (15.50 to 16.10), 20.0 A (19.70 to 20.30)

The standard sizes are 1, 2, 4, 7.5, 10, 15, 20, 25 and 30 kW. The 50 kW and 70 kW sizes are for replacement only (1.2.4). The standard input is single phase, 60 Hz (3.3.4). The AC allows other voltages, frequencies and sizes if the unit meets all requirements (1.2.4).

Where airfields use a CCR

The FAA recommends series circuits with isolation transformers for HIRL, MIRL and MITL systems. It recommends parallel circuits for LIRL (AC 150/5340-30J 2.6.2). Base-mounted fixtures must use series circuits (2.6.1.4). The advantages of a series circuit are uniform lamp brightness, fewer cold-start burnouts and in-rush currents, and no shutdown from an unintentional ground (2.6.2.1).

The AC names the CCR for other systems:

  • Runway centerline and touchdown zone lights use a 6.6 A circuit for a total load of 30 kW or less. Above that they use a 20 A circuit. The CCR size covers each fixture load plus the losses in the feed cable (3.4.3.2.2 and 3.4.3.2.3).
  • Taxiway centerline lights and clearance bars use a Class 1, Style 2 CCR (4.8.5.2).
  • Stop bars and runway guard lights use a Class 1, Style 1 CCR (4.8.7.2 and 4.8.6.1.1).
  • A Style B PAPI runs from an L-828 CCR with a 6.6 A output. A dedicated CCR with five steps is the preferred method (7.5.4.12 and 7.5.4.14.2).
  • A series-powered omnidirectional approach lighting system (ODALS) uses 6.6 A for high, 5.5 A for medium and 4.8 A for low intensity (7.5.3.1.6).

Load limits

Four limits apply to the load on a CCR.

  • The monitor works when the load is between 50 and 100 percent of the CCR rating. Each lamp and its isolation transformer may load the circuit with 10 to 200 W. All fixtures should be the same (AC 150/5345-10H 3.5b and 3.5l).
  • Devices on the series circuit must be certified. A non-certified device can cause a poor power factor, unexpected CCR shutdowns and start-up problems (AC 150/5340-30J 1.6).
  • An LED fixture on a CCR must have a true power factor of at least 0.7 (EB 67D 2.5.1).
  • In a Style B PAPI circuit, a CCR raises its output current as lamps burn out. This is critical when the load is under 50 percent of the CCR rating. A lamp bypass device stops the runaway effect, and the FAA recommends it for Style B PAPIs on resonant-type CCRs (AC 150/5340-30J 7.5.4.17).

A CCR can also emit electromagnetic interference that degrades other navigation equipment (AC 150/5340-30J 2.6.3.1). The FAA classes it as an incidental radiator (AC 150/5345-10H 3.3.12).

Protection and monitoring

A CCR must have:

  • an open-circuit device that opens the primary switch within 2 seconds
  • an over-current device that operates within 5 seconds at 5 percent over-current and within 1 second at 25 percent
  • lightning arresters at the input and output terminals
  • an input circuit that has no electrical connection to the output circuit

(AC 150/5345-10H 3.3.9, 3.3.10 and 3.4.12)

A plate on the cabinet door warns the technician to remove input and control power. This applies before opening the cabinet or interrupting the output circuit (3.4.14).

An L-829 regulator includes a monitor. The monitor detects these faults (Table 3):

  • loss of input power
  • shutdown by a protective circuit
  • a drop of 10 percent or more in the volt-amperes delivered to the circuit
  • wrong output current for the selected step
  • failure of a preset number of lamps

For identical lamps, the preset number is adjustable from four to ten. The monitor waits at least 5 seconds before it shows most faults (3.5i and 3.5m). After the preset number of lamps fail, the monitor can switch to a degraded mode. It then clears the fault indication and raises it again after a further one to five lamps fail (3.5n and 3.5o). All of these faults are electrical.

The regulator has local and remote control. It must work with a remote control circuit of 10,000 ft (3,000 m) of #19 AWG cable (3.3.7). A CCR can connect to a computerized airfield lighting control and monitoring system (ALCMS). The optional monitoring points can then report local or remote status and loss of primary power (3.5, note).

Efficiency, power factor and environment

The minimum efficiency at full load and top step is 90 percent below 30 kW and 92 percent at 30 kW (3.3.2). The power factor is at least 0.90 up to 10 kW and at least 0.95 above 10 kW (3.3.3). The equipment must run continuously at -40 to 55 degrees C. It must also run at 10 to 95 percent relative humidity and at altitudes up to 2,000 m (3.2).

Checks and safety

AC 150/5340-26C 5.2 sets this routine for a CCR:

  • Daily: check the control equipment and the remote control on each brightness step.
  • Weekly: visit each vault and check cleanliness and condition.
  • Monthly: record the input voltage and current, and record the output current on each step. Use a high accuracy true RMS ammeter and compare the values with the allowed ranges.
  • Semi-annual: inspect for loose connections and signs of overheating. If you suspect an overload, measure the output load.
  • Annual: test the dielectric strength of the oil in an oil-filled unit. Run a short-circuit test and an open-circuit test.

New oil should have a dielectric strength of 30 kV or more, and 22 kV is the minimum acceptable level (5.2.5).

Series circuits are dangerous. The AC says to assume that a circuit has power until you prove otherwise. Check for current with a true RMS clamp-on ammeter before you break a circuit. Never open a live series circuit (2.4.1). Do not measure the voltage across the output of a regulator without a load connected (5.2.4). Only qualified electricians may make these measurements.

Standards

The FAA specification is AC 150/5345-10H. It is mandatory only for projects that receive federal airport grants, and a recommendation otherwise (paragraph 4). ICAO Annex 14 requires the electrical systems to leave the pilot with adequate guidance after an equipment failure (8.1.2). It recommends a monitoring system that shows the operational status of the lighting systems (8.3.1).

CS-ADR-DSN has no CCR specification. It specifies a secondary power supply for the lighting aids in Table S-1 (S.880) and recommends a monitoring system for the lighting systems (S.890). Regulation ADR.OPS.C.015(a) requires a maintenance programme for the electrical systems. GM1 ADR-DSN.S.885 points to ICAO Doc 9157 Part 5 for guidance.

IEC 61820-3-2:2023 covers power converters for series-circuit ground lighting. It replaces IEC 61822:2009.

Why it matters for inspection

A drone survey measures the lights, not the regulator. The brightness of each light depends on the CCR step, so compare lights only at the same brightness and step. Monitoring in the regulator reports electrical status only. It does not report the light output of a fixture.

Frequently Asked Questions

What does a constant current regulator do?
It supplies a series lighting circuit with a fixed current for each brightness step. The regulator changes its output voltage as the load changes, so the current stays inside the allowed range. For a 6.6 A regulator the full-brightness range is 6.50 to 6.70 A.
What does CCR stand for in aviation?
CCR stands for constant current regulator. At an airport it is the power supply of a series lighting circuit. The FAA specification calls it type L-828 without monitoring or L-829 with monitoring.
Why do airfield lights use series circuits with a CCR?
A series circuit gives uniform lamp brightness. It also reduces cold-start burnouts and in-rush currents, and an unintentional ground does not shut the system down. The FAA recommends series circuits with isolation transformers for HIRL, MIRL and MITL systems.
What are the CCR classes and styles?
Class 1 has a 6.6 A output and Class 2 has a 20 A output. Style 1 has three brightness steps and Style 2 has five. Type L-828 is a regulator without monitoring, and L-829 is a regulator with monitoring.
What does a CCR monitor detect?
It detects loss of input power, a protective shutdown and wrong output current. It detects a drop of 10 percent or more in the power delivered to the circuit. It also detects failure of a preset number of lamps. The preset number is adjustable from four to ten identical lamps.
What happens to a CCR circuit when a lamp fails?
The other lights stay lit at the same current. When a filament opens, the isolation transformer keeps the primary series circuit closed. The CCR monitor reports a lamp fault only after a preset number of lamps fail.
Is a CCR the same as a constant current regulator IC?
No. An airfield CCR is a cabinet power supply. It has a 6.6 A or 20 A output and standard sizes of 1 to 30 kW for new designs. At full load its output reaches thousands of volts. It is not a semiconductor part.
How do you check a constant current regulator?
Measure the output current on every brightness step each month with a true RMS ammeter and compare it with the allowed range. The FAA also lists yearly short-circuit and open-circuit tests, and an oil test for oil-filled units. Only qualified staff may do them.

This is a reference entry. TarmacView provides drone inspection services and doesn't sell the equipment or materials described in this glossary.

Get Started Is every runway light still aimed and working? Drone inspection of edge, threshold and centreline lights, fixture by fixture, with output relative to the row and an out-of-tolerance list your maintenance team can act on the same day.
Keep reading

Learn more

06 PAGES

Related terms

03 TERMS
Intensity Step
glossary

Intensity Step

An intensity step is a preset brightness level of an airfield light, set as a percentage of full brightness. FAA step values and lamp currents, 3-step and 5-step CCRs, and how inspection checks them.

Constant Current
glossary

Constant Current

Constant current describes an electrical principle where a power source maintains a fixed, regulated current to its load, regardless of load resistance or input voltage variations. This is essential for applications like LED lighting, battery charging, and industrial systems where precise current is vital for performance, safety, and longevity.

Voltage Regulator
glossary

Voltage Regulator

A voltage regulator keeps an output voltage steady. It compares the output with a reference and corrects the error. Linear and switching types, aircraft use.

Further reading

03 ARTICLES
How Often Does Airfield Lighting Need Photometric Testing?
How Often Does Airfield Lighting Need Photometric Testing?
blog

How Often Does Airfield Lighting Need Photometric Testing?

How often airfield lighting is photometrically tested: no Part 139 interval, a twice-yearly floor on precision runways, monthly FAA tables and what a…

OCT 23 2026 8 MIN
What a Regulator Actually Accepts as Evidence
What a Regulator Actually Accepts as Evidence
blog

What a Regulator Actually Accepts as Evidence

Regulators rarely name an accepted instrument. What they accept is a dated, traceable record showing that the aerodrome's own agreed procedure was…

AUG 15 2026 8 MIN