What is a circuit breaker?
A circuit breaker is an overcurrent protective device that protects the conductors of an electrical circuit. A fuse is the other device that does this job.
How a circuit breaker works
A circuit breaker carries the circuit current through a switch that it can open by itself. The US Department of Energy defines a breaker for 600 V or less as a device that opens and closes a circuit by non-automatic means. It also opens the circuit automatically on a set overcurrent, without injury to itself, when it is used within its rating.
Overcurrent is any current above the rating of the equipment or the current capacity of the conductor. It comes from an overload, a short circuit or a ground fault. An overload is a current above the normal full load that lasts long enough to cause dangerous heat. A short circuit or a ground fault is not an overload.
Most low-voltage breakers use two trip elements in one housing:
- Thermal trip. The current heats a bimetallic strip. The strip bends and trips a spring-loaded switch. Heating is slow, so this element answers a sustained overload. A separate element handles a large surge.
- Magnetic trip. A small electromagnet pulls the strip down at once in a large current surge. This element answers a short circuit.
A breaker with both elements is a thermal-magnetic breaker. The Spanish term is interruptor termomagnético. FAA guidance for airfield lighting names this type for the power distribution panel.
Circuit breaker, fuse and the other protective devices
A fuse and a breaker both interrupt the current to protect conductor insulation and to limit the fire risk. In a fuse, a metal filament melts and breaks the connection. In a breaker, the trip elements open a switch.
Two other devices look similar but sense different faults:
- Ground-fault circuit interrupter (GFCI). It senses current that leaves through any path other than the proper conductor. A fuse or a breaker trips only when the fault is greater than its own rating, so it cannot give this protection. A Class A GFCI protects people and trips at 4 to 6 milliamperes. A Class B GFCI protects equipment and trips above 20 milliamperes.
- Arc-fault circuit interrupter (AFCI). It monitors the current waveform for harmful arcing in the wiring.
Arc-fault breaker versus a regular breaker
A regular breaker responds to the size of the current.
An AFCI breaker adds electronics. The US Consumer Product Safety Commission describes the difference between normal and harmful arcs:
- Normal arcs, such as those from a switch or a motor, repeat in each 60 Hz cycle.
- Harmful arcs have a non-periodic waveform with discontinuities.
The industry standard UL 1699 requires a trip when 8 half cycles of arcing occur within a 0.5 second window. An AFCI must not trip during normal current. It does not detect a glowing connection unless an arc or a ground fault is also present.
Ratings that matter when you choose a breaker
The rating of a breaker is more than its ampere value. The DOE handbook says to consider the interrupting current capacity of a fuse when the system has a significant fault current. The FAA applies the same idea to airfield lighting. It asks the designer to specify each component of the power system within its fault current withstand and interrupting ratings. A short circuit analysis shows the fault current at the service entrance, the switchboards and the panel boards.
In FAA airfield lighting guidance
FAA AC 150/5340-30J treats the breaker as part of the power distribution system for airfield lighting. It sets these rules:
- All lighting circuits count as continuous loads. The feeder conductors and the overcurrent protective device, a circuit breaker or a fuse, are sized at 125 percent of the full load current. For example, a circuit with a full load of 40 A needs a device and conductors sized for 50 A (40 times 1.25).
- The fuses or circuit breakers on a Precision Approach Path Indicator (PAPI) feeder must be within the equipment ratings.
- Circuit breakers in the power distribution panel are thermal-magnetic, molded case, permanent trip, with a 100-ampere minimum frame.
- A circuit breaker that is not in an FAA specification must conform to NFPA 70, the National Electrical Code (NEC).
- The constant current regulator (CCR) assembly, which powers a series lighting circuit, has open circuit and over current protective devices of its own.
- Separately installed circuit breakers may control a circuit selector switch remotely. The selector switch picks short segments of taxiway centerline lighting circuits.
After installation, the inspector checks that the fuses and circuit breakers have the proper rating.
Where a drone fits
The breakers are in the electrical vault and the distribution panels. A drone does not inspect them. TarmacView does not inspect circuit breakers. A drone inspects the lights and the surfaces out on the airfield, and a person checks the vault.
Frequently Asked Questions
- What is a circuit breaker?
- A circuit breaker is a device that opens a circuit by itself when the current goes above a set value. The US Department of Energy defines a breaker for 600 V or less in two parts. It opens and closes a circuit by non-automatic means. It also opens the circuit automatically on a set overcurrent without injury to itself.
- Is a circuit breaker the same as a fuse?
- No, but they have the same purpose. Both are overcurrent protective devices, and AC 150/5340-30J allows either one to protect a lighting feeder. In a fuse, a metal filament melts and breaks the connection. In a breaker, a bimetallic strip or an electromagnet trips a spring-loaded switch.
- How does a thermal-magnetic circuit breaker work?
- It has two trip elements. A bimetallic strip heats with the current, bends and trips the switch after a delay, which handles a sustained overload. A small electromagnet pulls the strip at once in a large surge, which handles a short circuit. The Spanish term is interruptor termomagnético.
- What is the difference between an arc-fault breaker and a regular breaker?
- A regular breaker trips on current above its rating. An arc-fault circuit interrupter (AFCI) breaker also watches the current waveform for the non-repeating signature of a harmful arc. The UL 1699 standard calls for a trip when 8 half cycles of arcing occur within 0.5 seconds.
- What is the difference between a GFCI and a circuit breaker?
- A ground-fault circuit interrupter (GFCI) senses current that leaks to ground and trips on a small imbalance. A Class A GFCI protects people and trips at 4 to 6 milliamperes. A standard breaker trips only when the fault current is greater than the rating of the device.
- How large must the overcurrent protective device be for a lighting circuit?
- The FAA guidance sizes it at 125 percent of the full load current on the circuit. It treats all lighting circuits as continuous loads, so the conductors are sized to carry the same 125 percent.
- What is checked on circuit breakers when a lighting system is installed?
- The inspector checks that the fuses and circuit breakers have the proper rating. On a PAPI feeder, they must be within the equipment ratings.
- Does a drone inspect circuit breakers?
- No. The breakers are in the electrical vault and the distribution panels, and a person checks them there. A drone inspects the lights and surfaces out on the airfield.
References
- faa-ac-150-5340-30j
- AC 150/5340-30J, Design and Installation Details for Airport Visual Aids FAA
- doe-hdbk-1092-2013
- DOE Handbook, Electrical Safety, DOE-HDBK-1092-2013 US Department of Energy
- hyperphysics-breakers
- Breakers and Ground Wires HyperPhysics, Department of Physics and Astronomy, Georgia State University
- cpsc-afci
- New Technology for Preventing Residential Electrical Fires: Arc-Fault Circuit Interrupters (AFCIs) US Consumer Product Safety Commission (Lee, Trotta and King)
This is a reference entry. TarmacView provides drone inspection services and doesn't sell the equipment or materials described in this glossary.