What is an Electrical Transformer?
Electrical Transformer
An electrical transformer is a passive device that transfers energy between circuits by electromagnetic induction, usually to raise or lower an AC voltage.
How a transformer works
A transformer has two coils, the primary and the secondary, wound on a soft iron core. Alternating current in the primary winding makes a changing magnetic field. This field induces a voltage in the secondary winding (openstax-up2-15-6). A transformer works only with alternating current, because a steady current makes no changing field.
The ratio of the two voltages equals the ratio of the turns in the two windings. The current changes in the opposite direction. In an ideal transformer, the input power equals the output power (openstax-up2-15-6).
The turns ratio formula
Vs / Vp = Ns / Np, and Is = (Np / Ns) x Ip.
Here V is voltage, N is the number of turns, and I is current. The subscript p means primary and s means secondary.
Worked example. A pole transformer steps 12 kV down to 240 V. The turns ratio Ns / Np is 240 / 12,000, which is 1/50. The primary has 50 times as many turns as the secondary. A primary current of 2.0 A gives a secondary current of 50 x 2.0 A, which is 100 A (openstax-up2-15-6).
A second example. A 230 V supply feeds a primary with 1,000 turns. A 12 V secondary needs 1,000 x 12 / 230, about 52 turns.
Step-up and step-down transformers
A step-up transformer has more secondary turns than primary turns. It raises the voltage and lowers the current. A step-down transformer has fewer secondary turns. It lowers the voltage and raises the current (openstax-up2-15-6).
Power plants step the voltage up to as much as about 500 kV for long lines. A higher voltage carries the same power at a lower current, and line loss grows with the square of the current. In the 12 kV example, the line loses 2.0 A squared x 200 ohms, which is 800 W. Without the transformer, 100 A would lose 2 MW in the same line (openstax-up2-15-6).
Types of transformer
- Distribution transformer. The US Department of Energy defines it by voltage. The input is 34.5 kV or less and the output is 600 V or less. This is a US definition (doe-distribution-transformers). Liquid-immersed units run from 10 to 2,500 kVA and dry-type units from 15 to 2,500 kVA.
- Instrument transformer. A potential transformer steps a high voltage down by a precise ratio so a voltmeter can read it. A current transformer steps a line current down for an ammeter. A current transformer must never run with an open secondary, because the voltage can become dangerously high (kuphaldt-ac-9).
- Autotransformer. One tapped coil serves as both windings. It gives no electrical isolation (kuphaldt-ac-9).
- Tapped transformer. Taps connect partway along a winding and give different ratios. Tap switches are not built to carry full load current (kuphaldt-ac-9).
- Isolation transformer. A 1:1 unit that gives electrical isolation with no change in voltage or current (kuphaldt-ac-9). See circuit isolation .
Losses and efficiency
Good transformers can lose as little as about 1 percent of the power they transfer (openstax-up2-15-6). The losses come from three causes (kuphaldt-ac-9):
- Resistance of the winding wire, which makes heat.
- Eddy currents that flow in the iron core.
- Hysteresis in the magnetic core material.
Core saturation makes a transformer draw excess current and heat up. A transformer also draws a large inrush current when first connected, so its overcurrent protection is slow-acting (kuphaldt-ac-9).
Transformers in airfield lighting
An aerodrome power supply can include a distribution network with transformers and switchgear. ICAO Annex 14 Volume I (section 8.1) and EASA GM1 ADR-DSN.S.875 both say so. The EASA maintenance programme should include transformers and regulators.
Many airfield lights run on a series circuit that a constant current regulator (CCR) powers. The FAA recommends series circuits with isolation transformers for high and medium intensity runway edge lights and medium intensity taxiway lights. It recommends parallel circuits for low intensity runway edge lights. For runway centerline and touchdown zone lights, the FAA gives a 20-ampere or 6.6-ampere series circuit. Each light fixture has its own isolation transformer. The manufacturer sizes it to match the lamp.
The isolation transformer separates the light unit from the high voltage of the series circuit. When a lamp filament opens, the isolation transformer keeps the primary series circuit continuous. The FAA specifies the L-830 type for 60 Hz and the L-831 type for 50 Hz. A series L-810 obstruction light has no film cutout, so it needs an isolation transformer with each lamp.
A precision approach path indicator (PAPI) also connects to the series circuit through an isolation transformer. The PAPI equipment does not include it. See the entries on the lighting circuit and the CCR .
Frequently Asked Questions
- What is an electrical transformer?
- An electrical transformer is a passive device that transfers energy between circuits by electromagnetic induction. It usually raises or lowers an AC voltage. It has two windings that share a magnetic core.
- How does a transformer change voltage?
- Alternating current in the primary winding makes a changing magnetic field, and this field induces a voltage in the secondary winding. The voltage ratio equals the turns ratio. A step-up transformer has more secondary turns than primary turns, and a step-down transformer has fewer.
- What is the difference between a step-up and a step-down transformer?
- A step-up transformer raises the voltage and lowers the current. A step-down transformer lowers the voltage and raises the current. In an ideal transformer the power stays the same on both sides.
- Why do power systems use transformers at high voltage?
- A higher voltage carries the same power at a lower current, and line loss grows with the square of the current. In the OpenStax example, a 200 ohm line loses 800 W at 12 kV and 2.0 A. At 240 V and 100 A it would lose about 2 MW.
- What is an instrument or voltage transformer?
- An instrument transformer scales a high voltage or current down to a value that a meter can read. A potential transformer steps voltage down by a precise ratio. A current transformer steps current down. Never open the secondary winding of a current transformer while it carries current.
- What does an isolation transformer do in airfield lighting?
- It separates the light unit from the high voltage of the series circuit. If a lamp filament opens, the isolation transformer keeps the primary series circuit continuous, so the other lights stay on. The FAA specifies the L-830 type for 60 Hz and the L-831 type for 50 Hz.
- Why are series circuits used for runway lights?
- The FAA lists uniform lamp brightness, fewer cold-start burnouts and in-rush currents, and no shutdown from an unintentional ground. It also lists a lower installation cost on long runways, generally over 4,000 ft (1219 m). It recommends series circuits with isolation transformers for high and medium intensity runway edge lights. Low intensity lights may use parallel circuits.
References
- openstax-up2-15-6
- University Physics Volume 2, section 15.6 Transformers OpenStax, Rice University
- kuphaldt-ac-9
- Lessons in Electric Circuits, Volume II (AC), Chapter 9, Transformers Tony R. Kuphaldt, open textbook
- doe-distribution-transformers
- Distribution transformers US Department of Energy, Office of Energy Efficiency and Renewable Energy
- faa-ac-150-5340-30j
- AC 150/5340-30J, Design and Installation Details for Airport Visual Aids FAA
- faa-ac-150-5370-10h
- AC 150/5370-10H, Standard Specifications for Construction of Airports FAA
- easa-ear-aerodromes
- Easy Access Rules for Aerodromes (Regulation (EU) No 139/2014), including CS-ADR-DSN Issue 7 EASA
- icao-annex-14-vol-i
- Annex 14 to the Convention on International Civil Aviation, Volume I, 9th edition ICAO
This is a reference entry. TarmacView provides drone inspection services and doesn't sell the equipment or materials described in this glossary.